PowerUP ONE 10 kVA
True double conversion online technology
Online UPSs are the most suitable choice, especially for computers and other sensitive devices. These types of UPSs completely isolate your sensitive devices from the network, charge their batteries with electricity from the network, and feed your connected sensitive devices with the help of various filters. As a result, all unwanted situations that may occur in the network are filtered by the online UPS and your sensitive devices are fed with clean energy.
| Specification | Details |
|---|---|
| Phase | One phase + Neutral + Earth |
| Rated Voltage | 220 / 230 / 240 Vac |
| Voltage Range | 120 ~ 276 Vac |
| Frequency Range | 50 Hz (45–55 Hz) / 60 Hz (54–66 Hz), automatic selection |
| Current (THDi) | ≤3% (linear load); ≤5% (non-linear load) |
| Bypass Voltage Range | 220Vac: +25% max (optional +10%, +15%, +20%)230Vac: +20% max (optional +10%, +15%)240Vac: +15% max (optional +10%)Minimum voltage: −45% (optional −20%, −30%)Bypass frequency range: ±1%, ±2%, ±4%, ±5%, ±10% |
| Power Factor | >0.99 (input THDv ≤1%) |
| Phase | One phase + Neutral + Earth |
| Rated Voltage | 220 / 230 / 240 Vac |
| Power Factor | 0.9 |
| Voltage Regulation | ±1.0% |
| Frequency | Normal mode: same as mainsBattery mode: 50 / 60 Hz ±0.1% |
| Crest Factor | 3:1 |
| THD | ≤2% (linear load); ≤5% (non-linear load) |
| Efficiency | <92% |
| Type & Quantity | 12V 9Ah × 16 |
| Charging Current | 1.0 A |
| Transfer Time | Mains → Battery: 0 msMains → Bypass: 0 ms |
| Overload (AC Mode) | 60 min @ 105–110% load10 min @ 110–125% load1 min @ 125–150% load>200 ms @ 150% load |
| Overload (Battery Mode) | 10 min @ 105–110% load1 min @ 110–125% load>200 ms @ 125% load |
| Overload (Bypass Mode) | 63A fuse |
| Over Temperature | Alarm |
| Battery Low | Alarm and shutdown |
| Test | Via software |
| EPO | UPS shuts down immediately |
| Battery Management | Smart battery management |
| Dimensions (D × W × H) | 460 × 191 × 720 mm |
| Weight | 121 kg |
| Status LED & LCD | Mains mode, Bypass mode, Battery low, Battery faulty, Overload, Fault |
| LCD Panel | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Battery temperature |
| Voice & Display Alarm | Mains error, Battery low, Overload, System error |
| Operating Temperature | 0°C ~ 40°C |
| Humidity | 0–95% non-condensing |
| Altitude | <1500 m |
| Noise Level | <55 dB @ 1 meter |
| Interfaces | USB, RS232, SNMP card (optional) |
Виж още UPS Tuncmatik
Виж всички UPS в категорията
| Изходяща мощност: | 10000 VA |
|---|---|
| Тип: | ON Line |
| Формфактор: | Tower |
- 5
0 ревюта
- 4
0 ревюта
- 3
0 ревюта
- 2
0 ревюта
- 1
0 ревюта



UPS Eaton 5PX 2200i RT3U G2, 2200VA/2200W, Line-Interactive, Rack/Tower1334.34 €
/2609.75 лв
UPS APC Smart-UPS, 1500VA/1000W, Line Interactive, 2U1316.61 €
/2575.07 лв
UPS Eaton 9E 3000i Rack (9E3000IR), 3000VA/2700W, LCD дисплей, On-Line, Rack1291.81 €
/2526.56 лв