ARTronic Titanium 10kVA
Икона в кампания
ARTronic Titanium 10kVAempty image 1empty image 2empty image 3

UPS ARTronic Titanium 10kVA, 3.1, ON Line, RS232, 3Phase in ->1Phase Out, 2г. гаранция

id 4023 Код: UPS10000ONLINE31
  • Модел: 10kVa 3.1
  • Марка: Artronic
  • Изходяща мощност: 10000 VA
  • Формфактор: Tower
  • Гаранция: 24 месеца
  • Наличност: Стар продукт
    ОписаниеХарактеристикиРевюта / Въпроси
    ARTon Titanium Series 3.1 10 - 15 - 20 kVA

    • VFI Topology Class 1 Double Conversion UPS
    • Graphic LCD Display and Touchpad Control Keys
    • Green Energy with Input Power Factor Correction (PFC)
    • Automatic Restart & Cold Start Function
    • Network Supported Monitoring & Control Software
    • SNMP & AS400 Network Monitoring Options
    • Silent & Economic Operation with Adjusted Fan Speed
    • Integrated Maintenance Bypass Switch
    • 3 Units in Paralel / Redundant Operation

    ARTon Titanium 3.1-10 kVA

    Capacity (VA / Watt) - 10000 VA / 7000 W
    3 In Parallel Capacity (VA / Watt) - 30000 VA / 21000 W

    INPUT - RECTIFIER

    Voltage & Voltage Range - 380 VAC, 3 Phase + Neutral
    Voltage Tolerance - 304 ? 478 VAC ± 3%
    Power Factor - ? 0.95
    Current (nominal) - 13 A / Phase - 39 A
    Frequency & Frequency Range - 50 Hz, 46 ~ 54 Hz, Adjustable to work with Any Generator

    OUTPUT - INVERTER and BYPASS

    Load Power Factor Range - 0.65 ~ 1.0

    Voltage & Voltage Tolerance - 220 / 230 / 240 VAC ± 1%

    Dynamic Response - Maximum Deviation ? 5% at 50% - 100 - 50% Load Change

    Recovery Time - 60 mili seconds to be with in ± 1% Static Tolerance at 0-100-0 % Load Change

    Total Harmonic Distortion (THD) - ? 2% at linear load, ? 6% at non linear load
    Frequency & Frequency Range - 50 Hz, ± 0.05 Hz Battery Operation

    Voltage Waveform - Pure Sine Wave
    Crest Factor - 3 : 1

    Over Load - 10 minutes for 105 ~130%, > 130% Transfer to Bypass after 1 second, Shutdown after 1 minute (in Line Mode)

    Short Circuit Protection - Electronic short circuit protection

    Bypass & Transfer Time - Standard Static Bypass, 0 (zero) for Line Mode to Battery and Inverter to Bypass Mode

    Bypass Tolerance & Adjustment - 176 ? 261 VAC Adjustable, Bypass can be Disable or Enable to use in Standby Mode


    BATTERY

    Type & Placement - Maintenance Free Dry Type Battery, Internal or External Regarding to Demand

    Capacity & Quantity - 12 V 9 Ah x 20 pieces

    Backup Time (100% / 50% Load) - 6 / 15 minutes

    Nominal / Charge Voltage - 240 / 274 VDC ± 1%
    End of Discharge Voltage - 220 VDC ± 3 VDC

    Battery Charge Current & Charging Time - Standard 2 A Charge Current for 6-10 kVA, 7-8 hours Charge Time to 90% Capacity after Discharge, 4.2 A Charge Current for 3.1 10-15-20 kVA


    INDICATORS & CONTROL PANEL

    Type - Graphic LCD Panel

    Control Panel - Touchpad Buttons (On/off, Audible Alarm Disable, Up/Down, Enter)

    Measurements & Warnings - UPSStatus, Input / Output Voltage & Frequency, Load %, Battery Capacity & Voltage, Warning & Alarm Messages

    Indications (LCD) - Mimic Diagram for Energy Flow, Measurements, Warnings, Faults, Adjustment


    PROTECTIONS

    Overload - Electronic Protection, Load Transfer to Bypass without any break after Overload period

    Short Circuit - Automatic Inverter Shutdown

    Over Temperature - Load transfer to Bypass for 90°C Internal Temperature, Transfer back to Inverter when Internal Temperature < 80°C

    Modem / Network Protection - Surge protection for Modem / Network line


    AUDIBLE ALARMS

    Warning Type and Warnings - Buzzer, Mutable with Audible Alarm Disable; Different Audible Signals for Battery Operation, Battery Low Voltage, UPS Fault, Overload


    COMMUNICATIONS

    Interface & Protocol - Smart RS232 Communication with DB9 (female) Port, Optional SNMP & AS400

    Software - Free of Charge, Network Supported Monitoring & Control Software, Software Supports Windows 98/ME/NT/2000/XP/2003, Linux, Sun Solaris 7/8/9, IBM Aix 4.3 & 5.1x, HP-UX 11.x, Compaq True 64, SGI Irix, Free BSD, Unix Systems, MAC Supported


    GENERAL

    Efficiency - AC to AC At 100% - 89%

    Noise Level - ? 60 dBA

    Electro Magnetic Compatibility - EN 61000-4-2 (ESD), 4-3 (RS), 4-4 (EFT), 4-5 (surge), IEC 62040-2 (EMI)

    Operation Temperature & Humidity - 0 °C ~ 40 °C, maximum 20~90% (Non Condensed)

    Storage Temperature - -20 °C ~ +70 °C

    Protection Class - IP20

    Cooling Type - Forced cooling Fan with Adjusted Speed

    Operation Altitude - < 1000 meters (from the sea level)

    Dimensions (mm), W x H x D - 260 x 717 x 570

    Weight, without / with Battery (kg) - 38,5 / 104


    Software:

    Winpower Free of Charge, Network Supported Monitoring & Control Software, Software Supports Windows 98/ME/NT/2000/XP/2003, Linux, Sun Solaris 7/8/9, IBM Aix 4.3 & 5.1x, HP-UX 11.x, Compaq True 64, SGI Irix, Free BSD, Unix Systems, MAC Supported

    *Гаранция на устройството - 2 г.



    Виж още UPS Artronic
    Виж всички UPS в категорията
    Технически характеристики
    Изходяща мощност:  10000 VA
    Формфактор:  Tower
    Добави Ревю / Въпрос
    Оцени продукта или задай въпрос?
    0.00 от 0 ревюта
    • 5
      0 ревюта
    • 4
      0 ревюта
    • 3
      0 ревюта
    • 2
      0 ревюта
    • 1
      0 ревюта
    • Какво пазаруват другите Какво пазаруват другите
    • Какво пазаруват другите Най-продавани продукти
    • Какво пазаруват другите Промоционални продукти
    prev slider image prev slider hover image next slider image next slider hover image

    ARTronic Titanium 10kVA
    UPS ARTronic Titanium 10kVA, 3.1, ON Line, RS232, 3Phase in ->1Phase Out, 2г. гаранция
    ARTronic Titanium 10kVA
    prev slider image prev slider hover image
    • ARTronic Titanium 10kVA
    next slider image next slider hover image